if my closet is 83 cubic feet and i have a 115 cfm exhaust fan, it SHOULD keep my average closet temps very close to the room its pulling intake from right?
 
I'm trying to figure out the same thing and ran across this info of how to calculate what you need taking all the factors into account: Comes from this website: http://www.bghydro.com/BGH/static/articles/0606_vent.asp

How to size your exhaust fan
There are many calculations on the web for sizing a fan for ventilating grow rooms; however, what these calculations fail to take into consideration is the friction loss on carbon filters, increased temperatures from HID lights and CO2, etc. The following calculation can be used as a guide for sizing an exhaust fan for a growing area (keep in mind that this calculation will give you the lowest required CFM required to ventilate the grow room):

Step 1 – Room Volume
First the volume of the room needs to be calculated. To calculate multiply length x width x height of growing area e.g. A room that is 8' x 8' x 8' will have a volume of 512 cubic feet.

Step 2
– CFM Required
The fan should be able to adequately exchange the air in a grow room once every three minutes. Therefore, 512 cubic feet/3 minutes = 171 cfm. This will be the absolute minimum cfm for exchanging the air in a grow room.

Step 3
– Additional factors

Unfortunately, the minimum cfm needed to ventilate a grow room is never quite that simple. Once the grower has calculated the minimum cfm required for their grow room the following additional factors need to be considered:

  1. Number of HID lights – add 5% per air cooled light or 10-15% per non-air cooled light.
  2. CO2 – add 5% for rooms with CO2 enrichment
  3. Filters – if a carbon filter is to be used with the exhaust system then add 20%
  4. Ambient temperature – for hot climates (such as Southern California) add 25%, for hot and humid climates (such as Florida) add up to 40%.
Example 1:

In our 8’ x 8’ room we have 2 x 1000w air cooled lights, and we plan to use a carbon filter. We also plan to use CO2 in this room. The ambient temperature is 90°F, however, we will be using air from another room that is air-conditioned.

Minimum Required CFM to ventilate room
:

(CFM required for room – step 2) + (CFM required for room – step 2 x 10% (2 air cooled lights)) + (CFM required for room – step 2 x 5% (CO2)) + (CFM required for room – step 2 x 20% (Carbon Filter)) + (Ambient Temperature 0 (Air coming from air-conditioned room)).

= (171cfm) + (171cfm x 10%) +
(171cfm x 5%) + (171cfm x 20%) + ( 0 )

= 231cfm – this is the absolute minimum cfm required to ventilate your room.
 