What would i need to run a sub panel 80ft from the main one.. i want to run about 8 1000watt lights. What would i need? Want to do estimate on material myself then bring in a electrician
 

mr.schroederific

Well-Known Member
Stop being cheap and let him make the couple dollars in material. Your electrian is more important than GOD. You will get what you pay for. Stop being cheap
 

Final Phase

Well-Known Member
I got lucky, my brother is an electrician. He ran ALL wires through conduit into junction boxes that joined industrial timers. He called the company of the makers of the digital ballasts that are being used to adjust breakers to keep from blowing. Never had a problem, never worry about fires, etc. lighting up my dreams.
 

Nice1son

Member
8 100w hps lights and you're worried about paying a electrician, it's going to be nothing compared with the electricity bill.
 

Carolina Dream'n

Well-Known Member
8k pulls 40 amps(220v), so a 50 amp breaker will cover that. Your gonna need 48k btu in ac to cool that room. That pulls 40 amps(220v). Gonna need at least 2 20 amps(110v) in dehumidifiers to keep your environment right. Another 20 amps for anything else you'll need to run.

Id run it on a 150 amp subpanel.

Breakers-
50 amp (220v)breaker for lights
2 20 amp (220v) for mini split
3 20 amp (110v) for dehumidifier and miscellaneous items.
You'll need 12/2 for the 20 amp 220v, 12/3 for the 20 amp 110v. 6/2 for the 50 amp 220v.

Your electrician needs to decide on copper vs aluminum for your main feed.
 

Kev3200

Well-Known Member
8k pulls 40 amps(220v), so a 50 amp breaker will cover that. Your gonna need 48k btu in ac to cool that room. That pulls 40 amps(220v). Gonna need at least 2 20 amps(110v) in dehumidifiers to keep your environment right. Another 20 amps for anything else you'll need to run.

Id run it on a 150 amp subpanel.

Breakers-
50 amp (220v)breaker for lights
2 20 amp (220v) for mini split
3 20 amp (110v) for dehumidifier and miscellaneous items.
You'll need 12/2 for the 20 amp 220v, 12/3 for the 20 amp 110v. 6/2 for the 50 amp 220v.

Your electrician needs to decide on copper vs aluminum for your main feed.
Thanks Alot Brother! It's All I Needed
 